• Models of width 17.5 mm available with 2 or 3 poles. Models of width 22.5 mm with 3 poles also available.
• Conforms to EN standards. (TÜV approval)
• DIN track mounting possible.
last update: December 19, 2013
• Models of width 17.5 mm available with 2 or 3 poles. Models of width 22.5 mm with 3 poles also available.
• Conforms to EN standards. (TÜV approval)
• DIN track mounting possible.
last update: December 19, 2013
last update: January 10, 2013
Model | G9SB-200[]-[] | G9SB-3010 | G9SB-301[]-[] |
---|---|---|---|
Power supply voltage | 24 VAC/VDC: 24 VAC, 50/60 Hz, or 24 VDC
24 VDC: 24 VDC |
||
Operating voltage range | 85% to 110% of rated power supply voltage | ||
Power consumption | 1.6 VA/1.4 W max. | 1.7 W max. | 2.0 VA/1.7 W max. |
Model | G9SB-200[]-[] | G9SB-3010 | G9SB-301[]-[] |
---|---|---|---|
Input current | 25 mA max. | 60 mA max. * | 30 mA max. |
* Indicates the current between terminals A1 and A2.
Model Load |
G9SB-200[]-[] | G9SB-3010 | G9SB-301[]-[] |
---|---|---|---|
Resistive load | |||
Rated load | 250 VAC, 5 A 30 VDC, 5 A |
||
Rated carry current | 5 A |
Model | G9SB-200[]-[] | G9SB-3010 | G9SB-301[]-[] | |
---|---|---|---|---|
Contact resistance *1 | 100 mΩ | |||
Operating time *2 | 30 ms max. | |||
Response time *3 | 10 ms max. | |||
Insulation resistance *4 | 100 MΩ min. (at 500 VDC) | |||
Dielectric
strength |
Between different
outputs |
2,500 VAC, 50/60 Hz for 1 min | ||
Between inputs
and outputs |
||||
Between power
inputs and outputs |
||||
Vibration resistance | 10 to 55 to 10 Hz, 0.375-mm single amplitude (0.75-mm double amplitude) | |||
Shock
resistance |
Destruction | 300 m/s2 | ||
Malfunction | 100 m/s2 | |||
Durability *5 | Mechanical | 5,000,000 operations min. (at approx. 7,200 operations/hr) | ||
Electrical | 100,000 operations min. (at approx. 1,800 operations/hr) | |||
Failure rate (P level)
(reference value) |
5 VDC, 1 mA | |||
Ambient operating temperature | -25 to 55°C (with no icing or condensation) | |||
Ambient operating humidity | 35% to 85% | |||
Terminal tightening torque | 0.5 Nm | |||
Weight | Approx. 115 g | Approx. 135 g | Approx. 120 g |
*1. The contact resistance was measured with 1 A at 5 VDC using the voltage-drop method.
*2. Not including bounce time.
*3. The response time is the time it takes for the main contact to open after the input is turned OFF. Includes bounce time.
*4. The insulation resistance was measured with 500 VDC at the same places that the dielectric strength was checked.
*5. The durability is for an ambient temperature of 15 to 35°C and an ambient humidity of 25% to 75%.
last update: January 10, 2013
TITLE | DOCUMENT TYPE | SIZE |
G9SB | Catalog | 523 KB |
---|---|---|
G9SB-200-/301-/3010 Safety Relay Unit (ENG/JPN) |
Manual | 310 KB |