Compact Industrial SCARA
Compact Industrial Robot with light weight space saving arm. Its high speed operation is best suited for pick and place, labelling, tracking
• Four circuit protectors in one package
• Simple setting of current tripping values for each branch outputs in 0.1-A units
• Startup and shutdown sequence control
• Display and alarm functions (Input voltage, output current, run time, and over-temperature)
• Outputs conform to UL Class 2 (at 24 VDC, S8M-CP04-RS only)
• DIN Rail mounting
• RoHs-compliant
• Free Support Tool available
Model | S8M-CP04 | S8M-CP04-R | S8M-CP04-RS | ||
---|---|---|---|---|---|
Number of branches | 4 | ||||
I/O char- acter- istics |
Rated input voltage | 24 VDC (19.2 to 26.4 VDC) | |||
Allowable input current | 17.0 A max. | 16.0 A max. | |||
Maximum tripping output current (per branch output) |
4.0 A | 3.8 A | |||
Internal voltage drop *1 | 0.5 VDC max. (at 4.0 A) | 0.7 VDC max. (at 3.8 A) | |||
Output leakage current | 10 mA max. | ||||
Power con- sumption *2 |
4 branches output, normal operation |
10 W max. (at 4.0 A) | 15 W max. (at 3.8 A) | ||
4 branches output, tripping operation |
3 W max. | ||||
Func- tions |
Tripping |
Abnormal voltage tripping |
28.8 V (fixed), tripping alarm output | ||
Abnormal current tripping |
Setting range: 0.5 to 4.0 A (in 0.1-A units), tripping alarm output |
Setting range: 0.5 to 3.8 A (in 0.1-A units), tripping alarm output |
|||
Tripping alarm output |
Transistor output 30 VDC max., 50 mA max., leakage current: 0.1 mA max., residual voltage: 2 V max. |
||||
Alarms | Overvoltage | Setting range: 20.0 to 28.8 V (in 0.1-V units), alarm output | |||
Undervoltage | Setting range: 18.0 to 26.4 V (in 0.1-V units), alarm output | ||||
Overcurrent |
Setting range: 0.5 to 4.0 A (in 0.1-A units), alarm output |
Setting range: 0.5 to 3.8 A (in 0.1-A units), alarm output |
|||
Run time |
Setting range: 0.0 to 99.9 kh (in 0.1-kh units), alarm output (The alarm output is disabled if the time is set to 0.0 kh.) |
||||
Alarm output |
Transistor output 30 VDC max., 50 mA max., leakage current: 0.1 mA max., residual voltage: 2 V max. |
||||
Temper- ature |
Temperature | Setting range: 25 to 80°C, over-temperature output | |||
Over- temperature output |
Transistor output 30 VDC max., 50 mA max., leakage current: 0.1 mA max., residual voltage: 2 V max. |
||||
Display | Input voltage |
Display range: 17.0 to 30.0 V Display accuracy: 2% rdg ±1 digit max. |
|||
Output current |
Branch output display range: 0.0 to 4.0 A Peak output current display range:0.0 to 10.0 A Total current display range: 0.0 to 40.0 A Display accuracy: 5% FS (4 A) ±1 digit max. |
||||
Run time |
Display range: 0.0 to 99.9 kh Display accuracy: 2% rdg ±1 digit max. |
||||
Temperature |
Display range: -10 to 100°C Display accuracy: 2°C ±1 digit max. |
||||
External tripping input | 19.2 to 30 VDC, minimum signal width: 10 ms, tripping within 20 ms of input | ||||
Startup sequence |
Can be enabled/disabled for each branch output, setting range: 0.0 to 99.9 s in 0.1-s units. |
||||
Shutdown sequence |
Can be enabled/disabled for each branch output, setting range: 0.0 to 99.9 s in 0.1-s units. |
||||
Communications | None | Supported (RS-232C) | |||
Sampling period | 1 ms | ||||
Other |
Ambient operating temperature |
Refer to the derating curve in Engineering Data (with no condensation or icing) | |||
Storage temperature | -25 to 65°C | ||||
Ambient operating humidity |
25% to 85% (storage humidity: 25% to 90%) | ||||
Dielectric strength |
1.0 kVAC for 1 min (between all charged sections and all non-charged sections; detection current: 20 mA) 500 VAC for 1 min (between all I/O and I/O signals/communications; detection current: 20 mA) 500 VAC for 1 min (between all I/O signals and communications; detection current: 20 mA) 500 VAC for 1 min (between input signals and all output signals; detection current: 20 mA) |
||||
Insulation resistance |
100 MΩ min. (between all charged sections and all non-charged sections) at 500 VDC 100 MΩ min. (between all I/O and I/O signals/communications) at 500 VDC 100 MΩ min. (between all I/O signals and communications) at 500 VDC 100 MΩ min. (between input signals and all output signals) at 500 VDC |
||||
Vibration resistance | 10 to 55 Hz, 0.375-mm single amplitude for 2 h each in X, Y, and Z directions | ||||
Shock resistance | 150 m/s2, 3 times each in ±X, ±Y, and ±Z directions | ||||
EMI |
Conducted Emission |
Conforms to EN 61204-3 Class B | |||
Radiated Emission |
Conforms to EN 61204-3 Class B | ||||
EMS | Conforms to EN 61204-3 High severity levels | ||||
Approved standards |
UL: | UL 508 (Listing), UL 60950-1 |
UL 508 (Listing, Class 2: Per UL 1310), UL60950-1 |
||
cUL: | CSA C22.2 No. 107.1 |
CSA C22.2 No. 107.1 (Class 2: Per No. 223) |
|||
cUR: | CSA No. 60950-1 | CSA No. 60950-1 | |||
EN/VDE: |
EN 50178 (= VDE 0160), EN 60950-1 (= VDE 0805 Teil 1) KOSHA S Mark |
EN 50178 (= VDE 0160), EN 60950-1 (= VDE 0805 Teil 1) KOSHA S Mark |
|||
Weight | 400 g max. |
Note: The image is the S8M-CP04-RS Model.
PFP-100N
PFP-50N
TITLE | DOCUMENT TYPE | SIZE |
S8M | Catalog | 1002 KB |
---|---|---|
S8M Digital Multicircuit Protector |
Manual | 3334 KB |
S8M Digital Multicircuit Protector (ENG/JPN) |
Manual | 7021 KB |
S8M-CP04-RS-30 Digital Multicircuit Protector (ENG/JPN) |
Manual | 568 KB |