Harmonized design and side-by-side mounting help delivering more compact control panels with additional functionality.
Harmonized design and side-by-side mounting help delivering more compact control panels with additional functionality.
The switch mode power supply, noise filter, and DC electronic circuit protector, all compliant with the “Value Design for Panel” concept, are made to be uniform in height to reduce dead space and enable control panel downsizing.
With its extensive product lineup and features such as electrical control CAD support and status visualization, the S8VK Series helps streamline processes in building equipment and control panels.
The S8VK Series offers both models with single phase (200-240 V) input and those with the more popular high-capacity three-phase input, allowing you to significantly reduce selection effort: just select a product with the input voltage and capacity best suited for your purpose.
OMRON provides the libraries for over 48,000 models*4, highest in the industry, to achieve the great
reduction of works for electrical design drawing and data creation.
*4. In the case of EPLAN, based on OMRON’s investigation as of 2020 December
*5. In the case of ZUKEN E3 series
By cooperating with various partners, we offer you more choices for your eCAD solutions.
E3.series is a product name of Zuken Inc. for their Electrical and Control Cable Design Solution.
EPLAN is a registered trademark of EPLAN Software & Service GmbH & Co. KG.
[S8VK-WA/WB]
S8VK-W power supplies notify users of their input voltage / load status via LED indicators and signal
output. This clarifies failure status and required actions, allowing users to troubleshoot more quickly
upon startup or during operation.
With excellent vibration and environmental resistance, S8VK power supplies can be used in a wide range of environments.
With the global expansion of production sites, control panels are expected to operate stably in vastly different environments
Control panels must comply with standards mandatory in their respective destinations
The S8VK Series enables stable facility operation even in environments with significant vibration.
Robustly designed for 5G vibration resistance twice the resistance of conventional industrial power
supplies.
S8VK power supplies can be safely transported by ship or over rugged terrain.
Ambient operating temperature of -40°C to 70°C
Operating humidity of up to 95%; PCBs coated for higher protection from dust
Complies with safety standards even at 3,000 m altitude *1
Complies with major standards such as UL and CSA as well as CE mark and other standards mandatory in specific regions for reliable use almost anywhere in the world. *1
*1. Refer to the datasheet of each product for information on supported standards.
Power rating | 240W | 480W | 960W | ||
---|---|---|---|---|---|
Output voltage | 24V | 24V | 24V | ||
Efficiency *1 | Three-phase 400 VAC input | 93% typ. | 94% typ. | 95% typ. | |
Two-phase 400 VAC input | 93% typ. | 94% typ. | 95% typ. | ||
Input
conditions |
Input voltage range *2 | Three-phase/two-phase 320 to 576 VAC, 450 to 810
VDC |
|||
Frequency *2 | 50/60 Hz (47 to 63 Hz) | ||||
Input current *1 | Three-phase 400 VAC input | 0.41 A typ. | 0.79 A typ. | 1.6 A typ. | |
Two-phase 400 VAC input | 0.75 A typ. | 1.5 A typ. | 3.0 A typ. | ||
Power factor *1 | Three-phase 400 VAC input | 0.9 min. | |||
Leakage current
*3 |
Three-phase 400 VAC input | 3.5 mA max. | |||
Inrush current *4 | Three-phase 400 VAC input | 1.9 A typ. | 3.3 A typ. | 10.6 A typ. | |
Output
character- istics |
Rated output current | 10 A | 20 A | 40 A | |
Power Boost Function | 15 A | 30 A | 60 A | ||
Voltage adjustment range *5 | 24 to 29.5 V (with V.ADJ) | 24 to 28 V
(with V.ADJ) |
|||
Ripple noise
voltage *6 |
Three-phase
380 to 480 VAC input |
100 mV p-p max.
at 20 MHz of bandwidth |
80 mV p-p max.
at 20 MHz of bandwidth |
50 mV p-p max.
at 20 MHz of bandwidth |
|
Input variation influence *7 | 0.5% max. | ||||
Load variation influence *8 | 1.5% max. | ||||
Temperature
variation influence |
200 to 240 VAC input | 0.05%/°C max. | |||
Startup time *9 | Three-phase 400 VAC input | 1,000 ms max. | |||
Output hold time
*9 |
Three-phase 400 VAC input | 30 ms typ. | 25 ms typ. | 20 ms typ. | |
Additional
functions |
Overload protection | Yes, automatic reset, intermittent operation
type Refer
to Overload Protection on below. |
|||
Overvoltage protection | Yes, 130% or higher of rated output voltage,
power
shut off (shut off the input voltage and turn on the input again), Refer to Overvoltage Protection on below. |
||||
Series operation | Yes (For up to two Power Supplies; external
diodes
required.) |
||||
Parallel operation | Yes (For up to two Power Supplies), Refer to
Parallel
Operation on Data Sheet. |
||||
INPUT OK Indicator | Yes (LED: Green) | ||||
DC OK Indicator | Yes (LED: Green) | ||||
Iout > 100% Indicator | Yes (LED: Yellow) | ||||
DC OK Signal Output | Yes (MOS FET relay output 30 VDC max., 50 mA max.) | ||||
Iout > 100% signal output | Yes (MOS FET relay output 30 VDC max., 50 mA max.) | ||||
Insulation | Withstand voltage | 3.0 kVAC for 1 min. (between all input terminals
and
all output terminals, signal output terminals), cutoff current 20 mA |
|||
2.5 kVAC for 1 min. (between all input terminals
and
PE terminals), cutoff current 30 mA |
|||||
1.0 kVAC for 1 min. (between all output
terminals,
signal output terminals and PE terminals), cutoff current 25 mA |
|||||
0.5 kVAC for 1 min. (between all output
terminals and
all signal output terminals), cutoff current 10 mA |
|||||
Insulation resistance | 100 MΩ min. (between all output terminals,
signal
output terminals and all input terminals / PE terminals) at 500 VDC |
||||
Environ-
ment |
Ambient operating temperature *10 | -40 to 70°C (Derating is required according to
the
temperature. Refer to Engineering Data on Data Sheet.) (with no condensation or icing) |
|||
Storage temperature | -40 to 85°C (with no condensation or icing) | ||||
Ambient operating humidity | 95% max. (Storage humidity: 95% max.) | ||||
Vibration resistance | 10 to 55 Hz, maximum 5 G, 0.42 mm single
amplitude
for 2 h each in X, Y, and Z directions |
||||
Shock resistance | 294 m/s2, 3 times each in ±X, ±Y, ±Z directions | ||||
Reliability | MTBF *11 | 170,000 hrs typ. | 160,000 hrs typ. | 140,000 hrs typ. | |
Expected life *12 | 10 years min. | ||||
Construc-
tion |
Weight | 890 g max. | 1,200 g max. | 1,800 g max. | |
Cooling fan | No | ||||
Degree of protection | IP20 by EN/IEC 60529 |
Power rating | 240W | 480W | 960W | ||
---|---|---|---|---|---|
Output voltage | 48V | 48V | 48V | ||
Efficiency *1 | Three-phase 400 VAC input | 93% typ. | 94% typ. | 96% typ. | |
Two-phase 400 VAC input | 93% typ. | 94% typ. | 95% typ. | ||
Input
conditions |
Input voltage range *2 | Three-phase/two-phase 320 to 576 VAC, 450 to 810
VDC |
|||
Frequency *2 | 50/60 Hz (47 to 63 Hz) | ||||
Input current *1 | Three-phase 400 VAC input | 0.41 A typ. | 0.78 A typ. | 1.6 A typ. | |
Two-phase 400 VAC input | 0.75 A typ. | 1.5 A typ. | 2.9 A typ. | ||
Power factor *1 | Three-phase 400 VAC input | 0.9 min. | |||
Leakage current
*3 |
Three-phase 400 VAC input | 3.5 mA max. | |||
Inrush current *4 | Three-phase 400 VAC input | 1.7 A typ. | 3.0 A typ. | 10.5 A typ. | |
Output
character- istics |
Rated output current | 5 A | 10 A | 20 A | |
Power Boost Function | 7.5 A | 15 A | 30 A | ||
Voltage adjustment range *5 | 48 to 56 V (with V.ADJ) | ||||
Ripple noise
voltage *6 |
Three-phase
380 to 480 VAC input |
50 m V p-p max.
at 20 MHz of bandwidth |
60 mV p-p max.
at 20 MHz of bandwidth |
60 mV p-p max.
at 20 MHz of bandwidth |
|
Input variation influence *7 | 0.5% max. | ||||
Load variation influence *8 | 1.5% max. | ||||
Temperature
variation influence |
380 to 480 VAC input | 0.05%/°C max. | |||
Startup time *9 | Three-phase 400 VAC input | 1,000 ms max. | |||
Output hold time
*9 |
Three-phase 400 VAC input | 30 ms typ. | 25 ms typ. | 20 ms typ. | |
Additional
functions |
Overload protection | Yes, automatic reset, intermittent operation
type Refer
to Overload Protection on below. |
|||
Overvoltage protection | Yes, 130% or higher of rated output voltage,
power
shut off (shut off the input voltage and turn on the input again), Refer to Overvoltage Protection on below. |
||||
Series operation | Yes (For up to two Power Supplies; external
diodes
required.) |
||||
Parallel operation | Yes (For up to two Power Supplies), Refer to
Parallel
Operation on Data Sheet. |
||||
INPUT OK Indicator | Yes (LED: Green) | ||||
DC OK Indicator | Yes (LED: Green) | ||||
Iout > 100% Indicator | Yes (LED: Yellow) | ||||
DC OK Signal Output | Yes (MOS FET relay output 30 VDC max., 50 mA max.) | ||||
Iout > 100% signal output | Yes (MOS FET relay output 30 VDC max., 50 mA max.) | ||||
Insulation | Withstand voltage | 3.0 kVAC for 1 min. (between all input terminals
and
all output terminals, signal output terminals), cutoff current 20 mA |
|||
2.5 kVAC for 1 min. (between all input terminals
and
PE terminals), cutoff current 20 mA |
|||||
1.0 kVAC for 1 min. (between all output
terminals,
signal output terminals and PE terminals), cutoff current 30 mA |
|||||
0.5 kVAC for 1 min. (between all output
terminals and
all signal output terminals), cutoff current 10 mA |
|||||
Insulation resistance | 100 MΩ min. (between all output terminals,
signal
output terminals and all input terminals / PE terminals) at 500 VDC |
||||
Environ-
ment |
Ambient operating temperature *10 | -40 to 70°C (Derating is required according to
the
temperature. Refer to Engineering Data on Data Sheet.) (with no condensation or icing) |
|||
Storage temperature | -40 to 85°C (with no condensation or icing) | ||||
Ambient operating humidity | 95% max. (Storage humidity: 95% max.) | ||||
Vibration resistance | 10 to 55 Hz, maximum 5 G, 0.42 mm single
amplitude
for 2 h each in X, Y, and Z directions |
||||
Shock resistance | 294 m/s2, 3 times each in ±X, ±Y, ±Z directions | ||||
Reliability | MTBF *11 | 170,000 hrs typ. | 160,000 hrs typ. | 140,000 hrs typ. | |
Expected life *12 | 10 years min. | ||||
Construc-
tion |
Weight | 890 g max. | 1,200 g max. | 1,800 g max. | |
Cooling fan | No | ||||
Degree of protection | IP20 by EN/IEC 60529 |
Output voltage (VDC) | 24 V/48 V | 24 V/48 V | 24 V/48 V | ||
---|---|---|---|---|---|
Standards
*14 |
Harmonic current emissions | Conforms to EN 61000-3-2 (three-phase/two-phase) *13 | |||
EMI | Conducted emissions | Conforms to EN 61204-3 Class B,
EN 55011 Class B (three-phase) Conforms to EN 61204-3 Class A, EN 55011 Class A (two-phase) |
|||
Radiated emissions | |||||
EMS | Conforms to EN 61204-3 high severity levels | ||||
Safety standards | UL 508 Listing
UL 62368-1 (Recognition) OVC II (≤ 3000 m) Pol2 CSA C22.2 No.62368-1 OVC II (≤ 3000 m) Pol2 EN/IEC 62477-1 OVC III (≤ 2000 m) OVC II (2000 m < and ≤ 3000 m) Pol2 EN/IEC 62368-1 OVC II (≤ 3000 m) Pol2 EAC (TR CU 004 / 2011, TR CU 020 / 2011) RCM (EN61000-6-4) Complies with PELV (EN/IEC 60204-1) Complies with EN/IEC 61558-2-16 BIS (IS13252 (Part1): 2010) |
||||
SEMI | Complies with SEMI F47-0706 (three-phase 380 to 480 VAC input) |
(Unit: mm)
Note: The front mounting bracket can be used for front, side-by-side mounting as well.
PFP-100N
PFP-50N
PFP-M
TITLE | DOCUMENT TYPE | SIZE |
S8VK-WB Catalog | Catalog | 4698 KB |
---|---|---|
Value Design for Panel Catalog | Catalog | 4698 KB |
S8VK-WB Datasheet | Datasheet | 1145 KB |