New undervoltage alarm function assists in determining causes of errors (S8VM-[][][]24A[]/P[] only).
New undervoltage alarm function assists in determining causes of errors (S8VM-[][][]24A[]/P[] only).
Power failure alarm function provides notification of output voltage errors (300-, 600-, and 1,500-W models only).
Broad range of possibilities with 8 capacities and 29 models to choose from.
RoHS-compliant
New, attentive design prevents screws from falling out of terminal block (except for output terminals of 300-, 600-, and 1,500-W models).
Finger protection prevents electric shock.
DIN Rail mounting.
Safety standards: UL508/60950-1, CSA C22.2 No. 14/No. 60950-1, EN50178, EN60950-1 (The 300-, 600-, and 1,500-W models will not conform to safety standards if the customer replaces the fan.)
Conforms to SEMI F47-0200 (when 200-V input is used).
Harmonic current emissions: Conforms to EN61000-3-2 (except for 15- and 30-W models).
Power rating | 15 W | 30 W | 50 W | 100 W | 150 W | ||
---|---|---|---|---|---|---|---|
Efficiency | 5-V models | 75% min. | 75% min. | 80% min. | 81% min. | 81% min. | |
12-V models | 78% min. | 79% min. | 79% min. | 81% min. | 81% min. | ||
15-V models | 78% min. | 79% min. | 79% min. | 81% min. | 81% min. | ||
24-V models | 80% min. | 81% min. | 80% min. | 82% min. | 83% min. | ||
Input | Voltage *1 | 100 to 240 VAC (85 to 265 VAC) | |||||
Frequency *1 | 50/60 Hz (47 to 63 Hz) | ||||||
Current | 100-V input | 0.5 A max. | 0.9 A max. | 0.8 A max. | 1.4 A max. | 2.0 A max. | |
200-V input | 0.25 A max. | 0.45 A max. | 0.4 A max. | 0.7 A max. | 1.0 A max. | ||
Power factor |
100-V input | --- | 0.98 min. | ||||
200-V input | --- | 0.94 min. | |||||
Harmonic current emissions |
--- | Conforms to EN 61000-3-2 | |||||
Leakage current |
100-V input | 0.4 mA max. (at rated output) | |||||
200-V input | 0.75 mA max. (at rated output) | ||||||
Inrush current *2 |
100-V input | 17.5 A max. (for cold start at 25 °C) | |||||
200-V input | 35 A max. (for cold start at 25 °C) | ||||||
Output |
Voltage adjustment range *3 |
-20% to 20% (with V. ADJ) (S8VM-[][][]24A[]/P[]: -10% to 20%) | |||||
Ripple |
3.2% (p-p) max. (5 V), 1.5% (p-p) max. (12 V), 1.2% (p-p) max. (15 V), 1.0% (p-p) max. (24 V), (at rated input/output voltage) |
3.2% (p-p) max. (5 V), 1.5% (p-p) max. (12 V), 1.2% (p-p) max. (15 V), 0.75% (p-p) max. (24 V), (at rated input/output voltage) |
|||||
Input variation influence | 0.4% max. (at 85 to 265 VAC input, 100%) | ||||||
Load variation influence (rated input voltage) |
0.8% max. (with rated input, 0 to 100% load) | ||||||
Temperature variation influence |
0.02%/°C max. | ||||||
Startup time *2 |
1,100 ms max. (at rated input/output voltage) |
800 ms max. (at rated input/output voltage) | |||||
Hold time *2 | 20 ms typ. (15 ms min.) (at rated input/output voltage) | ||||||
Additional functions |
Overload protection *2 |
105% to 160% of rated load current, voltage drop, intermittent, automatic reset |
105% to 160% of rated load current, voltage drop (12 V, 15 V, and 24 V), voltage drop, intermittent (5 V), automatic reset |
||||
Overvoltage protection *2 |
Yes *4 | ||||||
Undervoltage alarm indication |
Yes (color: Yellow (DC LOW1), red (DC LOW2)) (S8VM-[][][]24A[]/P[] only) | ||||||
Undervoltage alarm output | No |
Yes (S8VM-[][][]24A[]/P[] only) (Transistor output), 30 VDC max., 50 mA max. *8 |
|||||
Series operation | Yes for up to 2 Power Supplies (with external diode) | ||||||
Parallel operation | No (However, backup operation is possible. An external diode is required.) | ||||||
Remote sensing function | No | Yes | |||||
Other |
Ambient operating temperature |
Refer to the derating curve in See Engineering Data on Data Sheet (15-W, 30-W, 50-W, 100-W, 150-W Models). (with no icing or condensation) *2 |
|||||
Storage temperature | -25 to 65°C | ||||||
Ambient operating humidity |
30% to 85% (Storage humidity: 25% to 90%) | ||||||
Dielectric strength |
3.0 kVAC for 1 min. (between all inputs and outputs; detection current: 20 mA) 2.0 kVAC for 1 min. (between all inputs and PE/FG terminals; detection current: 20 mA) 500 VAC for 1 min. (between all outputs and PE/FG terminals; detection current: 100 mA) 500 VAC for 1 min. (between all outputs (except the detection output terminals) and detection output terminals; detection current: 20 mA) (S8VM- [][][]24A[]/P[] only) |
||||||
Insulation resistance |
100 MΩ min. (between all outputs and all inputs, PE/FG terminals) at 500 VDC |
||||||
Vibration resistance |
10 to 55 Hz, 0.375-mm single amplitude for 2 hours each in X, Y, and Z directions |
||||||
Shock resistance | 150 m/s2, 3 times each in ±X, ±Y, ±Z directions | ||||||
Output indicator | Yes (color: Green) | ||||||
EMI |
Conducted Emission |
Conforms to EN55011 Group1 Class B and based on FCC Class B *5 | |||||
Radiated Emission |
Conforms to EN55011 Group1 Class B *6 | ||||||
EMS | Conforms to EN61204-3 High severity levels | ||||||
Approved standards |
UL | UL508 (Listing), UL60950-1 | |||||
cUL | CSA C22.2 No.14 | ||||||
cUR | CSA No. 60950-1 | ||||||
EN/TÜV |
EN50178, EN60950-1 SELV (EN60950-1) According to VDE0160/P100 |
||||||
SEMI | SEMI F47-0200 (200 VAC input) | ||||||
Weight *7 | 180 g max. | 220 g max. | 290 g max. | 460 g max. | 530 g max. |
Power rating | 300 W | 600 W | 1,500 W | ||
---|---|---|---|---|---|
Efficiency | 5-V models | 77% min. | 77% min. | --- | |
12-V models | 78% min. | 79% min. | --- | ||
15-V models | 79% min. | 80% min. | --- | ||
24-V models | 81% min. | 81% min. | 82% min. | ||
Input | Voltage *1 | 100 to 240 VAC (85 to 265 VAC) | 100 to 240 VAC (85 to 265 VAC) | ||
Frequency *1 | 50/60 Hz (47 to 63 Hz) | ||||
Current | 100-V input |
4.0 A max. (5 V) 4.3 A max. (12 V, 15 V, and 24 V) |
8.0 A max. (5 V) 8.3 A max. (12 V, 15 V, and 24 V) |
20.0 A max. | |
200-V input |
2.0 A max. (5 V) 2.2 A max. (12 V, 15 V, and 24 V) |
4.0 A max. (5 V) 4.2 A max. (12 V, 15 V, and 24 V) |
11.0 A max. | ||
Power factor |
100-V input | 0.98 min. | 0.97 min. | ||
200-V input | 0.94 min. | 0.93 min. | |||
Harmonic current emissions |
Conforms to EN61000-3-2 | ||||
Leakage current |
100-V input | 0.4 mA max. | 1.5 mA max. | ||
200-V input | 0.75 mA max. | 1.5 mA max. | |||
Inrush current *2 |
100-V input | 20 A max. (for cold start at 25 °C) | |||
200-V input | 40 A max. (for cold start at 25 °C) | ||||
Output |
Voltage adjustment range *3 |
-20% to 20% (with V. ADJ) | |||
Ripple |
3.8% (p-p) max. (5 V), 2.0% (p-p) max. (12 V), 2.0% (p-p) max. (15 V), 1.25% (p-p) max. (24 V), (at rated input/output voltage) |
1.25% (p-p) max. *7, (at rated input/output voltage) |
|||
Input variation influence | 0.4% max. (at 85 to 265 VAC input, 100%) | ||||
Load variation influence (rated input voltage) |
0.6% max. (with rated input, 0 to 100% load) | ||||
Temperature variation influence |
0.02%/°C max. | ||||
Startup time *2 | 1,000 ms max. (at rated input/output voltage) | ||||
Hold time *2 | 20 ms typ. (15 ms min.) (at rated input/output voltage) | ||||
Additional functions |
Overload protection *2 |
105% to 160% of rated load current (5 V, 12 V, and 15 V), 120% to 160% of rated load current (S8VM-30024C), 115% to 160% of rated load current (S8VM- 60024C), voltage drop (12 V, 15 V, and 24 V), voltage drop, intermittent (5 V), automatic reset |
105% to 160% of rated load current (100 VAC), 155% to 200% of rated load current (200 VAC), voltage drop, automatic reset (Turns OFF when continuous for 5 s min.) *4 |
||
Overvoltage protection *2 |
Yes *4 | ||||
Overheat protection *2 | Yes *4 | ||||
Undervoltage alarm indication |
No | ||||
Undervoltage alarm output |
No | ||||
Power failure alarm indication |
Yes (color: Red) | ||||
Power failure alarm output |
Yes (Transistor output), 30 VDC max., 50 mA max. | ||||
Series operation | Yes for up to 2 Power Supplies (with external diode) | ||||
Parallel operation | Yes (up to 2 units) | ||||
Remote sensing function | Yes | ||||
Remote control function | Yes | ||||
Other |
Ambient operating temperature |
Refer to the derating curve in See Engineering Data on Data Sheet (300-W, 600-W, 1,500-W Models). (with no icing or condensation) *2 |
|||
Storage temperature | -25 to 65°C | ||||
Ambient operating humidity |
30% to 85% (Storage humidity: 25% to 90%) | ||||
Dielectric strength |
3.0 kVAC for 1 min. (between all inputs and outputs; detection current: 20 mA) 2.0 kVAC for 1 min. (between all inputs and PE terminals; detection current: 20 mA) 500 VAC for 1 min. (between all outputs and PE terminals; detection current: 100 mA) 100 VAC for 1 min. (between all outputs and RC terminals; detection current: 100 mA) 500 VAC for 1 min. (between all outputs and PF terminals; detection current: 20 mA) |
3.0 kVAC for 1 min. (between all inputs and outputs; detection current: 20 mA) 2.0 kVAC for 1 min. (between all inputs and FG terminals; detection current: 20 mA) 500 VAC for 1 min. (between all outputs and FG terminals; detection current: 300 mA) 100 VAC for 1 min. (between all outputs and RC terminals; detection current: 100 mA) 500 VAC for 1 min. (between all outputs and PF terminals; detection current: 20 mA) |
|||
Insulation resistance |
100 MΩ min. (between all outputs and all inputs, PE terminals) at 500 VDC |
100 MΩ min. (between all outputs and all inputs, FG terminals) at 500 VDC |
|||
Vibration resistance |
10 to 55 Hz, 0.375-mm single amplitude for 2 hours each in X, Y, and Z directions |
10 to 55 Hz, 0.15-mm single amplitude for 2 hours each in X, Y, and Z directions |
|||
Shock resistance | 150 m/s2, 3 times each in ±X, ±Y, ±Z directions | ||||
Output indicator | Yes (color: Green) | ||||
EMI |
Conducted Emission |
Conforms to EN55011 Group1 Class B and based on FCC Class B *5 |
Conforms to EN55011 Group1 Class A and based on FCC Class A *6 |
||
Radiated Emission |
Conforms to EN55011 Group1 Class B *5 |
Conforms to EN55011 Group1 Class A *6 |
|||
EMS | Conforms to EN61204-3 High severity levels | ||||
Approved standards *8 |
UL |
UL508 (Recognition) (5 V, 12 V, and 15 V) UL508 (Listing) (24 V), UL60950-1 |
UL508, UL60950-1 | ||
cUR | CSA C22.2 No.14 (24 V) | ||||
cUR | CSA No. 60950-1 |
CSA C22.2 No.14, CSA No. 60950-1 |
|||
EN/TÜV |
EN50178, EN60950-1 SELVE (EN60950-1) |
EN50178, EN60950-1 SELVE (EN60950-1) |
|||
SEMI | SEMI F47-0200 (200-VAC input) | ||||
Weight | 1,100 g max. | 1,700 g max. | 3,800 g max. |
last update: December 21, 2015
last update: December 21, 2015
TITLE | DOCUMENT TYPE | SIZE |
S8VM | Catalog | 8432 KB |
---|---|---|
S8VM (15/30/50/100/150 W) Switching Power Supply (1/2) |
Manual | 587 KB |
S8VM (15/30/50/100/150 W) Switching Power Supply (2/2) |
Manual | 3024 KB |
S8VM (300/600/1500 W) Switching Power Supply (1/2) | Manual | 1236 KB |
S8VM (300/600/1500 W) Switching Power Supply (2/2) |
Manual | 434 KB |
S82Y-VM30FAN/VM60FAN/VM15FAN Fan Unit |
Manual | 283 KB |