Power Controllers FAQ


Frequently asked questions and answers for General purpose Relays - Industrial Automation


Relays with Overlapping Contacts


Question

Can three G3PX Power Controllers for single-phase applications be combined for control of three-phase loads?


Answer

No.


Three-phase loads are controlled by each having a phase angle separated by 120°, so three G3PX Units for single-phase applications cannot be used. Always use a Three-phase Controller to control three-phase loads.



Sometimes the G3PX-260E[] can be used for an open delta configuration (see the connection diagram below).




Note:The G3PX-220E[]/240E[] (20 A/40 A) cannot be used.


G3PX Input Terminal Connection


Question

Which terminals should the G3PX Power Controller inputs be connected to?


Answer

It depends on the type of input.


1. Analog Inputs

(1) 4 to 20-mA or 1 to 5-V Inputs


Terminals: 4 and 5


Note:The terminals are the same (4 and 5) for both current and voltage inputs.


Input impedance: 250 Ω



(2) Analog Inputs Using External Main Setting



2. ON/OFF Pulse Inputs

Terminal numbers 3 to 5


(1) Power ON/OFF Pulse Signal Inputs


Example



(2) Contact ON/OFF Pulse Signal Inputs



Note:There is only one input of whatever kind. The G3PX may be damaged if there is more than one signal is input.

What is Soft Start?


Question

What is a soft start?


Answer

Soft start is a function that enables smoother starting by suppressing the inrush current when the load power supply is turned ON. Soft starts are particularly useful for loads with large inrush currents, such as halogen lamps.


The G3PX Power Controller has soft start, soft up, and soft down functions that adjust the soft start time and the up/down times using hardware adjustments. This prevents sudden changes to outputs, which shorten heat life


A halogen lamp has three to five times more inrush current if it does not have a soft start function. (The inrush current time is short.)


Such a large inrush current has a huge impact on the G3PX itself and the system.



If the halogen lamp is used with a soft-start function it gradually turns ON, starting with the smallest phase angle, as shown in Fig. 2.


This is how the inrush current is suppressed.



Difference between Various Controls in PID Control


Question

In PID control, what are the differences between ON/OFF time-sharing proportional control, cycle control, optimum cycle control, and phase control?


Answer
G3PX Phase Control

  1. The output amount is changed each half cycle, enabling high accuracy temperature control.
  2. More finely tuned control enables resistance to external disturbances and few heat shocks, thereby extending the service life of the heater.
  3. The gradient can be set as desired, and so the output amount can be set when a Power Controller is used in a set with a Temperature Controller.
  4. Inrush current can be suppressed by using a soft start or a constant-current circuit.
  5. Noise occurs due to phase control.

G32A-EA and Solid-state Relay Cycle Control

  1. The output cycle of the voltage output enables detailed control with a short cycle, which achieves temperature control with greater precision than ON/OFF time-sharing proportional control.
  2. Manual control without the use of Temperature Controllers can be achieved.

ON/OFF Time-sharing Proportional Control

  1. ON/OFF time-sharing proportional control is the most widely used control method in combination with Temperature Controllers.
  2. Frequently turning the power supply ON and OFF ill shorten the service life of the heater.
  3. This method is suitable for controlling items with a large heat capacity, which are difficult to heat and cool.


Number of G3PX Power Controller Connecting to a Temperature Controller


Question

How many G3PX Power Controllers can be connected to one Temperature Controller?


Answer
1. Current Outputs

Up to two G3PX Controllers can be connected in a serial drive. However, an OMRON Temperature Controller (allowable load impedance: 600 Ω) must be used.


2. Voltage Outputs


Power Controller: Consequences If 200 VAC is Applied to a 100 VAC Terminal


Question

If 200V is applied to the AC100V terminal, what will happen?


Answer

When the G3PX turns ON and a load current flows, a residual voltage is produced on the switching element.


The heating value will be obtained from the following formula.


Example:


Case of the G3PX-220EUN (with rated currents of 20A)


VRMS (residual voltage)=1.6V (output ON voltage drop in the brochure)


If the power consumption is indicated as P:


P=20A×1.6V


P=32W


This is the power consumption of the G3PX.


In terms of calorie 1cal/s equals 4.19W, therefore:


32W÷4.19 ≒ approx.7.6cal/s


The residual voltage means the voltage lost inside the semiconductor when it turns ON.


What is Power Regulator?


Question

What is a Power Regulator?


Answer

A Power Regulator is a device for regulating power. There are various types of Power Regulators for various types of power control. OMRON Power Regulators use phase control and receive signals from a Temperature Controller or variable resistor and performs precise heater control


Some Power Regulators are called Thyristor Units and SCR Units.


Power Controller: What is Gradient Setting?


Question

What is the gradient setting?


Answer

The gradient setting is a function for adjusting the output variation using internal or external variable resistors, as shown in the following diagram. The gradient setting function is separate from the temperature control signals and is used to refine the output amount.


If the internal and external variable resistor controls are used at the same time, the internal variable resistor setting will take precedence


Example:


If the internal gradient setting is 0%, the external gradient setting can be adjusted only between 0% and 80%.



Power Controller: Detecting Disconnection for Multiple Heaters


Question

What are the conditions for detecting disconnection for G3PX-2[][]EHN-CT Power Controllers that detect disconnection for multiple heaters?


Answer

The disconnection detection conditions are listed below.


1. The load current must be 1 A min.


2. The CT detection current must be 30% or higher of the rated maximum load current.


Note:Increase the number of CT turns if the CT detection current is 30% or less.


3. Up to five heaters can be connected (20% multiple heater disconnection detection characteristics)



Power Controller: Same Power Supply Used for both the Circuit and the Load


Question

Why is the same power supply used for both the circuit power supply and the load power supply?


Answer

The phase zero point must be detected to perform phase control. To detect the zero point, the phases must be the same. Phase difference may result in malfunctions. (The input signal and output amount will not match.)


Use 3-phase Power Supply for Single-phase Power Controller


Question

Is it possible to use a three-phase power supply for single-phase G3PX Power Controllers?


Answer

There is no problem if only one G3PX is used but the following issues arise if more than one G3PX is used. The G3PX-220E[]/240E[](20A/40A) use triac output elements.


If more than one single-phase models is connected to different phases in a three-phase power supply, the power supply distortion or phase control noise may make outputs unstable. (With G3PX-EH/-EHN/-EC Controllers this may cause disconnection/element ON fault detection, overcurrent detection, alarm malfunctions, etc.)


For these reasons, the power supply must be taken from the same phases if using a three-phase power supply. The G3PX-260(60A)E[] uses a thyristor for the output element and is not easily affected.


G3PX-220E[]/240E[] (20 A/40 A)



The following countermeasures can be used if it is not possible to take the power from the same phases.


1. Use the G3PX-260E[] (which uses a thyristor as the output element).


2. Use the G3PX-220DU (Three-phase Controller).


Power Controller: Constant-current Model Sometimes Having All Indicators ON


Question

Why does the constant-current model sometimes have all indicators ON?


Answer

A constant-current model will sometimes not be able to perform control if used with a current load much smaller than the rated current.


Possible Countermeasures:


1. Adjust the CUR LIM adjuster until one of the level indicators turns OFF.



2. If using 50% or less of the rated current, increase the number of turns of the wire on the CT.


Example:


50% of the rated current: 2 turns


25% of the rated current: 4 turns


Applicable models: G3PX-2[][]EC/G3PX-2[][]DC Power Controllers


Power Controller: Level Indicator


Question

What is a level indicator?


Answer

A level indicator is a series of 6 level LEDs used to visually check the output level. It is not a very accurate indicator, however, and only provides an indication of the load output.


To accurately find out the output amount, use a meter that displays the effective values of AC circuit voltage and current.



Power Controller: Minimum Load Current Value


Question

What is the minimum load current value that can be set?


Answer

The load current is limited to 1A at 100% output.


TRIAC or Thyristor output elements have a minimum holding current. If the load current is less than 1A, decrease in output signals cannot make output elements keep in the ON state, so that oscillating waveform may occur or they may not be turned ON.


Power Controller: Calorific Value of G3PX


Question

How much heating value flows from the Electrical Regulator "G3PX"?


Answer

When the G3PX turns ON and a load current flows, a residual voltage is produced on the switching element.


The heating value will be obtained from the following formula.


Example:


Case of the G3PX-220EUN (with rated currents of 20A)


VRMS (residual voltage)=1.6V (output ON voltage drop in the brochure)


If the power consumption is indicated as P:


P=20A x 1.6V


P=32W


This is the power consumption of the G3PX.


In terms of calorie 1cal/s equals 4.19W, therefore:


32W÷4.19≒approx.7.6cal/s


The residual voltage means the voltage lost inside the semiconductor when it turns ON.


Power Controller: Combine Single-phase Applications for Control of 3-phase Loads


Question

What is the constant-current function?


Answer

This is a function that protects the heater and the system by automatically suppressing excessively large inrush current, such as with pure metal heaters.


As shown in Figure 1, ten times the rated current flows when power is applied to pure metal heaters, for which molybdenum and tungsten are typical. (This current cannot be fully suppressed by using a long soft-start time.)


Figure 1 Flow without Constant-current Function

As shown in Figure 2, the constant-current circuit functions to automatically regulate to the current in response to the input signal. Inrush current is suppressed by reducing the ON phase.


(Overcurrent detection will operate and the switching elements will be protected if a large current flows that the constant-current circuit cannot suppress. If this occurs, the input signal will be cut off, and the level indicator will flash.)


Figure 2 Flow with Constant-current Function

Note: Protection is not provided in case of protection short circuit. Also use a quick-burning fuse.

Wiring between Temperature Controller and G3PX Power Controller


Question

What wiring should be used between a Temperature Controller and the G3PX Power Controllers?


Answer
1. Analog Control

Controlling with a 4 to 20-mA-output Temperature Controller



Note: Up to 2 drivable G3PX and a current output Temperature Controller can be used.
This is restricted, however, to Temperature Controllers with an allowable load impedance of 600 O.


Changing the Gradient for a Temperature Controller (4 to 20-mA Output)

Note: The gradient can be changed using either the internal or external gradient setting using the external adjuster.

2. ON/OFF Control
Changing Gradient Using a Voltage-output Temperature Controller


Note: The gradient can be changed using either the internal or external gradient setting.


Power Controller: Failure Detection Wiring


Question

How should failure detection be wired?


Answer

The G3PX Power Controller power supply should be wired from the circuit breaker or contactor to protect the circuit by operating the host circuit breaker or contactor using the G3PX failure detection relay output. The alarm output cannot be reset if it is wired from the secondary side.




Power Controller: Phase Control


Question

What is phase control?


Answer

Phase control is control method in which the output amount is changed each half cycle. It enables high-precision temperature control.



Analog control of the output power is possible by receiving a 4 to 20-mA current output signal from the Temperature Controller.


The high-precision control makes the Temperature Controller resistant to external interference and the small heat shock means the heater life can be extended.


Note: Noise is generated, however, because it is not a zero-cross circuit.


Power Controller: Protection Against Load Short-Circuiting


Question

For the Electrical Regulator "G3PX" with the constant-current function, can protection be provided with the G3PX against load short circuiting?


Answer

No. Protection is not provided.


If short-circuit current flows, the elements will be destroyed before the constant-current or overcurrent detection currents operate. To protect the G3PX from short-circuit accidents, connect a quick-burning fuse.

Note: Noise is generated, however, because it is not a zero-cross circuit.


Recommended fuses



Applicable Models: G3PX-2[][]EC/ G3PX-2[][]DC