1. Flow rates can be measured at the same time as power by inputting flow pulses. (Two inputs are supported.) To support energy-saving analysis, power consumption can be compared with the flow rate of air, gas, or other fluids with a single Unit.
last update: December 03, 2014
1. Flow rates can be measured at the same time as power by inputting flow pulses. (Two inputs are supported.) To support energy-saving analysis, power consumption can be compared with the flow rate of air, gas, or other fluids with a single Unit.
2. Pulse inputs can be counted, or used to measure the ON time. The consumption rate of a device can be measured by dividing the power consumption with the measured number of operations or operation time.
KM50 Power Monitors have a thermistor chip built onto the panel surface for easy measurement of the panel surface temperature.
The temperature display can be offset to match the room temperature to manage trends.
In addition to the consumed energy (total regenerative power consumption), generated power (total regenerative energy) can also be measured.
A single Power Monitor can measure equipment that effectively uses power generated by reverse motor rotation.
In addition to instantaneous reactive power, the total leading or lagging power consumption can also be measured.
Together with peak power measurements, this function aids with monitoring the power distribution equipment.
Automatic range switching enables high-accuracy measurements even for microcurrents.
Standby and stopped power can be accurately measured.
When measured at the distribution board, the total of the distributed values is almost the same as the base measurement.
You can measure microcurrents of ±75 mA with a CT with a rated current of 100 A. (Reference Value)
You can measure microcurrents of ±4 mA with a CT with a rated current of 5 A. (Reference Value)
Note: Reference values are typical values. Actual values may vary.
Measurements can be made on the primary side of an inverter.
Power consumption can be measured even after installing inverters which are widely used to save energy. This enables you to accurately grasp the effect obtained by introducing the inverter.
The total power consumption can be converted to the equivalent monetary cost.
Displaying the cost of the wasted energy can be used to support energy-saving measures.
Alarms can also be set up for generated power (regenerative power), current, voltage, power factor, or reactive power to assist plant monitoring.
Data can be saved as follows: 5-minute data for two days, 1-hour data for eight days, 1-day data for month, and 1-month data for one year.
*1. The data that is logged with a 5-minute cycle can be read out only by using RS-485 communications. Readout is not possible with key operations on the Power Monitor. *2. Up to 48 hours of data can be read out using communications.
Incorrect voltage wiring can be detected.
If any mistakes were made during installation, they are automatically detected, reducing the time required for checking after installation.
This also reduces the risk of having to restart when a mistake is found.
Up to 99 KM50 Power Monitors can be connected using RS-485 Modbus.
The energy use of each device can be managed with minimal wiring.
last update: December 03, 2014
last update: October 01, 2015
Model | KM50-C | |
---|---|---|
Applicable circuit | Single-phase two-wire, single-phase three-wire, and three-phase three-wire power | |
Rated power supply voltage |
100 to 240 VAC, 50/60 Hz The power supply voltage and measurement voltage input are shared (terminals 6 and 7). |
|
Allowable supply voltage range | 85% to 110% of rated power supply voltage | |
Allowable frequency range | 45 to 65 Hz | |
Power consumption | 7 VA max. | |
Rated input |
Rated input voltage |
100 to 240 VAC (single-phase, 2-wire): Line voltage 100/200 VAC (single-phase, 3-wire): Phase voltage/line voltage 100 to 240 VAC (3-phase, 3-wire): Line voltage |
Rated input current | 5 A, 50 A, 100 A, 200 A, 400 A, or 600 A (primary current of Special CT) * | |
Rated frequency | 50/60 Hz | |
Rated input power |
With 5-A CT: 2 kW With 50-A CT: 20 kW With 100-A CT: 40 kW With 200-A CT: 80 kW With 400-A CT: 160 kW With 600-A CT: 240 kW |
|
Allowable input voltage | 110% of rated input voltage (continuous) | |
Allowable input current | 120% of rated input current (continuous) | |
Rated input load |
Voltage input: 0.5 VA max. (excluding power supply) Current input: 0.5 VA max. (for each input) |
|
Time |
2010 to 2099 (Adjusted for leap year.) Accuracy: ±1.5 min/month (at 23 °C) |
|
Time backup period | 3 days (without power supply, at 23 °C) | |
Ambient operating temperature | -10 to +55 °C (with no condensation or icing) | |
Storage temperature | -25 to +65 °C (with no condensation or icing) | |
Ambient operating humidity | 25% to 85% | |
Storage humidity | 25% to 85% | |
Altitude | 2,000 m max. | |
Installation environment | Overvoltage category and measurement category: 2, Pollution level: 2 |
* A special output signal is output as the secondary current from the Special CT.
Model | KM50-C | ||
---|---|---|---|
Accuracy *1 |
Voltage |
± 1.0% FS ± 1 digit (at ambient temperature of 23 °C, rated input, and rated frequency). However, the accuracy is ± 2.0% FS ± 1 digit for the Vtr line voltage for three- phase, three-wire power and the Vrs line voltage for single-phase, three-wire power under the same conditions. |
|
Current |
± 1.0% FS ± 1 digit (at ambient temperature of 23 °C, rated input, and rated frequency). However, the accuracy is ± 2.0% FS ± 1 digit for the phase-S current for three-phase, three-wire power and the phase-N current for single-phase, three-wire power under the same conditions. |
||
Active power Reactive power |
± 2.0% FS ± 1 digit (at ambient temperature of 23 °C, rated input, rated frequency, and a power factor of 1) Reactive power formula: Reactive power = v × i × sin θ * "v" is the instantaneous voltage and "i" is the instantaneous current. θ is the phase difference between the voltage and current. |
||
Frequency |
± 0.3 Hz ± 1 digit (at ambient temperature of 23 °C, rated input, and rated frequency) |
||
Power factor |
±5.0% FS ±1 digit (at ambient temperature of 23 °C, rated input, rated frequency, and Power factor = 0.5 to 1 to 0.5) Power factor formula: Power factor = Active power/Apparent power * Apparent power = √ (Active power)2 + (Reactive power)2 |
||
Temperature |
± 5 °C two hours after the power is turned ON (after setting the offset to match the ambient environment) |
||
Low-cut current set value | 0.1% to 19.9% of rated current input (in 0.1% increments) | ||
Sampling cycle |
100 ms for measurement voltage at 50 Hz and 83.3 ms for measurement voltage at 60 Hz |
||
Temperature influence *1 |
± 1.0% FS ± 1 digit (percentage of power within operating temperature range, at ambient temperature of 23 °C, rated input, rated frequency, and power factor of 1) |
||
Frequency influence *1 |
±1.0% FS ±1 digit (percentage of power within rated frequency ±5 Hz, at ambient temperature of 23 °C, rated input, and power factor of 1) |
||
Influence of harmonics *1 |
± 0.5% FS ± 1 digit (at ambient temperature of 23 °C, error for superimposed 2nd, 3rd, 5th, 7th, 9th, 11th, and 13th harmonics for a content percentage of 30% for current and 5% for voltage of the basic wave) |
||
Insulation resistance |
1) Between all power circuits and all of the RS-485 terminals, OUT1, OUT2, event inputs, I/O commons, and transistor outputs: 20 MΩ max. (at 500 VDC) 2) Between all current and voltage inputs and all of the RS-485 terminals, OUT1, OUT2, event inputs, I/O commons, and transistor outputs: 20 MΩ max. (at 500 VDC) 3) Between all current and voltage inputs and the front case: 20 MΩ max. (at 500 VDC) 4) Between all power circuits and the front case: 20 MΩ max. (at 500 VDC) |
||
Dielectric strength |
1) Between all power circuits and all of the RS-485 terminals, OUT1, OUT2, event inputs, I/O commons, and transistor outputs: 2,800 VAC for 1 min 2) Between all current and voltage inputs and all of the RS-485 terminals, OUT1, OUT2, event inputs, I/O commons, and transistor outputs: 3,600 VAC for 1 min 3) Between all current and voltage inputs and the front case: 3,600 VAC for 1 min 4) Between all power circuits and the front case: 2,800 VAC for 1 min |
||
Vibration resistance |
Single amplitude: 0.35 mm, Acceleration: 50 m/s2, Frequency: 10 to 15 Hz, 10 sweeps for 8 min each along three axes |
||
Shock resistance | 150 m/s2, 3 times each in 6 directions (up/down, left/right, forward/backward) | ||
Weight | Approx. 150 g (Power Monitor only) | ||
Degree of protection |
Front panel: IP66 (when mounted to a panel), Rear case: IP20, Terminal section: IP00 |
||
Memory backup | EEPROM (non-volatile memory), No. of writes: 1,000,000 times | ||
Compliant standards |
EN61010-1 (IEC61010-1), EN61326-1 (IEC61326-1), UL61010-1, CAN/CSA- C22.2 No.61010-1 |
||
Event inputs |
Number of inputs |
Two event inputs The common terminal is shared with the OUT1 |
|
Voltage input |
High level: 4.75 to 30 VDC Low level: 0 to 2 VDC Input impedance: Approx. 2 kΩ |
||
No-voltage input |
ON resistance: 1 kΩ max. OFF resistance: 100 kΩ min. ON residual voltage: 8 V max. ON current (at 0 Ω ): 10 mA max. |
||
Minimum input time | 5 ms | ||
Transistor outputs |
Number of outputs |
5 open-collector outputs (two total power consumption pulse output or alarm output, and three, 3-state outputs) The total power consumption pulse output and alarm output use the same common terminal. The three, 3-state outputs use the same common terminal. |
|
Output capacity |
30 VDC, 30 mA max. ON residual voltage: 12 V max. OFF leakage current: 100 μ A max. |
||
Alarm output delay *2 | OFF delay: 0.0 to 99.9 s, ON delay: 0.0 to 99.9 s | ||
Characteristic operating time *3 |
±200 ms | ||
Commu- nications |
Communications method |
RS-485 (2-wire half-duplex) | |
Sync method | Start-stop | ||
Unit number setting | CompoWay/F: 0 to 99, Modbus: 1 to 99 | ||
Baud rate | 1.2, 2.4, 4.8, 9.6, 19.2, 38.4 kbps | ||
Transmission code | CompoWay/F: ASCII, Modbus: Binary | ||
Data length | 7, 8 bits | ||
Stop bit length | 1, 2 bits | ||
Vertical parity | Even, odd, or none | ||
Maximum transmission distance |
500 m | ||
Maximum number of connected Power Monitors |
CompoWay/F: 31, Modbus: 99 | ||
EMC (Industrial electromagnetic environment) |
EMI EN61326-1 |
Radiated RF Electromagnetic Field: CISPR 11 class A Conducted Emission: CISPR 11 class A |
|
EMS EN61326-1 |
Electrostatic Discharge Immunity: EN61000-4-2 Electromagnetic Field Immunity: EN61000-4-3 Fast Transient/Burst Noise Immunity: EN61000-4-4 Surge Immunity: EN61000-4-5 Conducted Disturbance Immunity: EN61000-4-6 Power Frequency Magnetic Field Immunity: EN61000-4-8 Voltage Dip and Interruption Immunity: EN61000-4-11 |
*1 The error of the Special CT is not included.
*2 There may be error in the alarm output OFF delay and ON delay due to the measurement sampling cycle.
*3 This is the error in the operating time of the alarm output (including the error in the alarm output ON/OFF delays and
output terminal switch operating time).
Model |
KM20- CTF- 5A |
KM20- CTF- 50A |
KM20- CTF- 100A |
KM20- CTF- 200A |
KM20- CTF- 400A |
KM20- CTF- 600A |
---|---|---|---|---|---|---|
Rated primary current | 5 A | 50 A | 100 A | 200 A | 400 A | 600 A |
Secondary winding | 3,000 turns | 6,000 turns | 9,000 turns | |||
Application frequency | 10 Hz to 5 kHz | |||||
Insulation resistance | Between output terminal and external case: 50 MΩ min. (at 500 VDC) | |||||
Dielectric strength | Between output terminal and external case: 2,000 VAC for 1 min | |||||
Protective element | 7.5 V clamp element | |||||
Allowable number of connections/disconnections |
100 times | |||||
Inner diameter | 7.9 dia. max. | 9.5 dia. max. | 14.5 dia. max. | 24.0 dia. max. | 35.5 dia. max. | |
Operating temperature and humidity range |
-20 to +60 °C 85% (with no condensation) | |||||
Storage temperature and humidity range |
-30 to +65 °C 85% (with no condensation) |
* If you use a flat cable, select the cable based on the dimensions of the CT.
Model | KM20-CTF-CB3 |
---|---|
Cable length | 3 m |
Note: Either use the CT Cable specified by OMRON or use 1.25-B3A crimp terminals and AWG22 wire from J.S.T. Mfg. Co., Ltd.
last update: October 01, 2015
last update: December 03, 2014
Rated primary current of 5 A: KM20-CTF-5A
Rated primary current of 50 A: KM20-CTF-50A
Rated primary current of 100 A: KM20-CTF-100A
Rated primary current of 200 A: KM20-CTF-200A
Rated primary current of 400 A: KM20-CTF-400A
Rated primary current of 600 A: KM20-CTF-600A
KM20-CTF-CB3 (3 m)
last update: December 03, 2014
TITLE | DOCUMENT TYPE | SIZE |
KM50-C1-FLK | Catalog | 1856 KB |
---|---|---|
KM50 smart power monitor cj-series general-purpose serial connection guide (RS-485 CompoWay/F Communications) | Technical Guide | 3401 KB |
KM50-C Smart power monitor |
Instruction Manual | 218 KB |
KM50-C Smart power monitor |
Instruction Manual | 165 KB |